# Danfoss supermarket refrigeration managers have an unpatched CVSS 9.8 flaw (CVE-2026-129713). What to do

> CISA says a stack overflow in an unauthenticated web handler on Danfoss AK-SM 8xxA system managers (firmware 5.4.0 and earlier) could let attackers run code without logging in. No fix exists yet; Danfoss says one is coming in 5.5.x. These are the same controllers caught up in this autumn's supermarket attacks, so get them off the internet now.

Published Nov 27, 2026 by TechMeasured Staff · Security · Canonical: https://techmeasured.com/security/danfoss-ak-sm-8xxa-cve-2026-129713-unpatched-9-8-supermarket-controllers-what-to-do

**CISA has published an advisory for an unpatched, critical vulnerability in Danfoss AK-SM 8xxA refrigeration system managers, the boxes that run cold rooms and display cases in many supermarkets.** The flaw, CVE-2026-129713, is a stack-based buffer overflow in a web (CGI) handler that does not require a login, according to write-ups of CISA advisory ICSA-26-328-03 by [Hive Security](https://hivesecurity.gitlab.io/blog/danfoss-ak-sm-8xxa-cve-2026-129713-unpatched-response/), [Cyber Security News](https://cybersecuritynews.com/danfoss-refrigeration-controller-flaw/) and [Mallory](https://mallory.ai/stories/01a213b0-1010-7f80-bdbd-6ea14305b771). Those outlets date the advisory to November 24. We could not open the CISA advisory or Danfoss's own advisory (DSA-2026-12-01) from this run, so the details below come from those reports.

Why it matters: there is no patch, and these controllers are already targets. Attackers changed defrost settings at supermarkets in France in October and hit at least 115 stores in seven countries on November 2, according to [The Hacker News](https://thehackernews.com/2026/11/hackers-exploit-10-vulnerabilities.html) and Mallory. CISA says it knows of no public exploitation of this particular CVE, and none of the outlets ties the attacks to it. But a pre-login bug in a device that already draws attackers means owners should act before a fix ships.

## The flaw at a glance

| | |
|---|---|
| CVE | CVE-2026-129713 (CISA ICSA-26-328-03) |
| Products | Danfoss AK-SM 8xxA system managers; BleepingComputer names the 820A, 850A and 880A, per Hive Security |
| Affected firmware | 5.4.0 and earlier |
| Type | Stack-based buffer overflow (CWE-121, per Hive), unauthenticated CGI handler |
| Severity | CVSS 9.8 (v3.1) / 9.3 (v4.0), per Hive Security and DEV Community |
| Exploited? | No known public exploitation, per CISA as reported by Hive, Cyber Security News and Mallory |
| Fix | None yet. Danfoss plans a fix in firmware 5.5.x, with no date given |
| Credited to | Carlo Meijer of Midnight Blue, per Hive, Cyber Security News and Mallory |

A crafted HTTP or HTTPS POST request corrupts memory and restarts the device's web server. The Hacker News quotes CISA's own careful wording: the bug could allow "hypothetically potential arbitrary code execution" with web-server privileges. In other words, a crash is certain; code execution is a credible possibility CISA has not shown.

Danfoss says the 5.5.x release will also remove the option to turn off Strict Mode, a hardened setting, according to The Hacker News, Hive and Cyber Security News.

## Where the bug came from

Security firm Midnight Blue published research on the AK-SM 800A on November 11, according to Hive. Hive Security and [DEV Community](https://dev.to/damiano_builds/six-zero-days-in-one-hour-why-researchers-say-patching-wont-save-the-danfoss-ak-sm800a-17hc) report that the researchers found six pre-authentication memory bugs in firmware 5.3.2 in under an hour. They also found secure boot was not enabled and the main application runs as root. Midnight Blue's report was titled "Don't bother patching," DEV Community says. Its point was that the platform has deeper design problems than any single fix covers.

Two points remain unclear. Hive says CISA does not say which of the six findings CVE-2026-129713 covers. DEV Community describes all six as filed under the one CVE. Midnight Blue also claims a separate overflow that could bypass Strict Mode. Hive notes this has not been independently reproduced.

There is also a conflict about versions. DEV Community says Germany's BSI treated firmware 5.4.0 as the only safe version in mid-November. CISA's advisory, as reported by every other outlet we read, lists 5.4.0 and earlier as affected. We follow CISA: there is no fixed version today.

## How many are exposed

No outlet gives a reliable global count. Hive cites the BSI as saying a "low three-digit number" of these systems was reachable directly from the internet in Germany alone. DEV Community cites Censys data from November 10 showing "hundreds" of Danfoss systems online, adding that many may be honeypots set up after the attacks.

Older units are worse off. Hive says the AK-SM 800 and AK-SC 355, which are past software support, will get no firmware fix at all.

## Don't confuse this with the KEV entries

On November 25, CISA added three **older** Danfoss AK-SM 800A flaws to its Known Exploited Vulnerabilities catalog: CVE-2023-25914 (path traversal), CVE-2023-25915 (command injection) and CVE-2025-41450 (authentication bypass), The Hacker News reports. Those do have firmware fixes, with federal deadlines of November 28 (25914, 25915) and December 9 (41450). We covered that batch in our [Mitel MiCollab KEV story](/security/mitel-micollab-awv-five-cves-cisa-kev-exploited-patch-10-3-0-18-what-to-do). CVE-2026-129713 is a separate, newer bug, and it is not in the KEV catalog.

## What to do

If you run Danfoss AK-SM system managers, or a contractor runs them for you:

1. **Take them off the public internet.** CISA recommends firewalls, network segmentation and a VPN or other protected network for remote access, with that VPN kept up to date (via Cyber Security News and Hive).
2. **Check exposure from outside your network.** Don't rely on the installer's word. Hive recommends checking from an external connection whether the web interface answers.
3. **Turn on Strict Mode** if it is off. Hive says it has been the default since firmware 4.0. Keep in mind the unconfirmed bypass claim above, so Strict Mode alone is not enough.
4. **Patch the three KEV-listed older flaws** now if you haven't, then plan to update to 5.5.x when Danfoss releases it. Hive notes the upgrade may drop remote browser sessions.
5. **Use strong, unique passwords** and named accounts for each user, and rotate shared ones (Danfoss via Cyber Security News; Hive).
6. **Watch the equipment, not just the network.** Hive recommends keeping logs on the network side and checking that connected equipment is working as intended, which for these systems means cases and cold rooms holding temperature.
7. **Plan to replace AK-SM 800 and AK-SC 355 units.** Per Hive, they won't get a fix.

For background on the attack campaign and the FBI and CISA warning to US grocers, see our [earlier guide](/security/fbi-cisa-refrigeration-controller-attacks-danfoss-xweb-grocery-what-to-do). Watch for Danfoss's 5.5.x release date and any update from CISA if exploitation of CVE-2026-129713 is seen.


## Sources

1. [Hive Security — Six Danfoss Zero-Days, One CVE, and a Fix That Has Not Shipped](https://hivesecurity.gitlab.io/blog/danfoss-ak-sm-8xxa-cve-2026-129713-unpatched-response/)
2. [The Hacker News — Hackers Exploit 10 Vulnerabilities Across Mitel, Juniper, Vates, and Danfoss Products](https://thehackernews.com/2026/11/hackers-exploit-10-vulnerabilities.html)
3. [Cyber Security News — Critical Danfoss Refrigeration Controller Flaw Could Allow Remote Code Execution Without Authentication](https://cybersecuritynews.com/danfoss-refrigeration-controller-flaw/)
4. [Mallory — CISA Warns of Unpatched Danfoss Controller Flaw Allowing Potential Unauthenticated RCE](https://mallory.ai/stories/01a213b0-1010-7f80-bdbd-6ea14305b771)
5. [DEV Community — Six Zero-Days in One Hour: Why Researchers Say Patching Won't Save the Danfoss AK-SM800A](https://dev.to/damiano_builds/six-zero-days-in-one-hour-why-researchers-say-patching-wont-save-the-danfoss-ak-sm800a-17hc)